Flow coefficient

The flow coefficient of a device is a relative measure of its efficiency at allowing fluid flow. It describes the relationship between the pressure drop across an orifice, valve or other assembly and the corresponding flow rate.

Mathematically the flow coefficient Cv (or flow capacity rating of valve) can be expressed as:

where:

In more practical terms, the flow coefficient Cv is the volume (in US gallons) of water at 60° F that will flow per minute through a valve with a pressure drop of 1 psi across the valve.

The use of the flow coefficient offers a standard method of comparing valve capacities and sizing valves for specific applications that is widely accepted by industry. The general definition of the flow coefficient can be expanded into equations modeling the flow of liquids, gases and steam as follows:

Coefficient of discharge is the ratio of actual flow rate to theoretical discharge.

For gas flow in a pneumatic system the Cv for the same assembly can be used with a more complex equation.[1][2] Absolute pressures (psia) must be used for gas rather than simply differential pressure.

For air flow at room temperature, when the outlet pressure is less than 1/2 the absolute inlet pressure, the flow becomes quite simple (although it reaches sonic velocity internally). With Cv = 1.0 and 200 psia inlet pressure the flow is 100 standard cubic feet per minute (scfm). The flow is proportional to the absolute inlet pressure so that the flow in scfm would equal the Cv flow coefficient if the inlet pressure were reduced to 2 psia and the outlet were connected to a vacuum with less than 1 psi absolute pressure (1.0 scfm when Cv = 1.0, 2 psia input).

Flow factor

The metric equivalent flow factor (Kv; commonly used in Europe and Asia) is calculated similarly, but the rate of flow is expressed in units of cubic meters per hour, and the pressure in bar. Kv can be calculated from Cv using the equation [3]

It can also be obtained directly in metric: The kv factor or value as it is also called is defined in VDI/VDE Richtlinien No. 2173. A simplified version of the definition is: The kv factor of a valve indicates "The water flow in m3/h, at a pressure drop across the valve of 1 kg /cm2 when the valve is completely open. The complete definition also says that the flow medium must have a specific gravity of 1000 kg /m3 and a kinematic viscosity of 10−6 m2/s. e.g. water

where:[4]