Talcher–Kolar HVDC system

Talcher–Kolar HVDC system
Location
Country India
State Orissa, Karnataka
Coordinates 21°06′01″N 85°03′49″E / 21.10028°N 85.06361°E / 21.10028; 85.06361 (Talcher–Kolar HVDC system – Talcher converter station)
13°10′39″N 78°07′00″E / 13.17750°N 78.11667°E / 13.17750; 78.11667 (Talcher–Kolar HVDC system – Kolar converter station)
From Talcher, Orissa (Eastern Region)
To Kolar, near Bangalore (Southern Region)
Ownership information
Owner Power Grid Corporation of India
Construction information
Installer of substations Siemens
Commissioned 2003
Technical information
Type Transmission
Type of current HVDC
Total length 1,450 km (900 mi)
Power rating 2000 MW
DC Voltage ±500 kV
Number of poles 2

The Talcher–Kolar HVDC system, otherwise known as the East–South interconnection II is a 1450 km HVDC transmission connection between the eastern and southern regions in India. The system has a transmission voltage of ±500 kV and was originally put into service in March 2003,[1] with a rated power of 2000 MW. In 2007 the scheme was upgraded to 2500 MW.

The Talcher–Kolar HVDC system is owned by Power Grid Corporation of India and the converter stations were built by Siemens.

The scheme is a conventional bipolar system with overhead lines for the high-voltage conductors and ground return for the neutral current.

Block diagram of a bipolar system with ground return

Ground electrodes

The scheme includes two ground electrodes, of ring construction, located at Rohila, 28.5 km northeast of the Talcher converter station and at Chikkadasarahalli, 30 km northwest of the Kolar converter station.[1]

However, the soil conditions at some distance from the electrode at Chikkadasarahalli were later found to have higher than expected soil resistivity. These geological effects gave rise to problems with DC currents flowing into the neutral connections of transformers at nearby AC substations, which required the addition of DC blocking devices.

Sites

Site Coordinates
Talcher converter station 21°06′01″N 85°03′49″E / 21.10028°N 85.06361°E / 21.10028; 85.06361 (Talcher–Kolar HVDC system – Talcher converter station)
Rohila electrode station 21°12′11″N 85°19′05″E / 21.20306°N 85.31806°E / 21.20306; 85.31806 (Talcher–Kolar HVDC system – Rohila electrode station)
Kolar converter station 13°10′39″N 78°07′00″E / 13.17750°N 78.11667°E / 13.17750; 78.11667 (Talcher–Kolar HVDC system – Kolar converter station)
Chikkadasarahalli electrode station 13°20′19″N 77°53′49″E / 13.33861°N 77.89694°E / 13.33861; 77.89694 (Talcher–Kolar HVDC system – Chikkadasarahalli electrode station)

References

  1. 1 2 Nayak R.N., Sasmal R.P., Sen S., Pelly B., Riedel P., Experience with blocking devices during monopolar operation of +/- 500kV, 2000MW Talcher–Kolar HVDC system in India, CIGRÉ session, Paris, 2006, paper reference B4-204.