Rotary phase converter

A simple homemade phase converter

A rotary phase converter, abbreviated RPC, is an electrical machine that produces three-phase electric power from single-phase electric power. This allows three phase loads to run using generator or utility-supplied single-phase electric power.

Original "Kandó" design

The first locomotive with a phase converter (only for demonstration purposes)
The Kandó phase converter (1933)
The "Kandó" locomotive, the first locomotive using a phase converter system

At the beginning of the 20th century, there were two main principles of electric railway traction current systems:

  1. DC system
  2. 16 2/3 Hz three-phase system

These systems used serial traction motors. All of them needed a separated supply system or converters to the standard 50 Hz electric network. Kálmán Kandó recognized that the electric traction system must be supplied by single-phase 50 Hz power from the standard electric network, and it must be converted in the locomotive to three-phase power for traction motors. He created an electric machine called a synchronous phase converter, which was a single-phase synchronous motor and a three-phase synchronous generator with common stator and rotor. It had two independent windings. The winding placed closer to the rotor is a three-phase (or variable-phase) synchronous generator and the other is a winding of a single-phase synchronous motor. The winding of the motor takes the power from the overhead line and the generator provides the power for the three (or more) phase traction motors.

The direct feed from a standard electric network makes the system less complicated than the earlier systems and makes possible simple recuperation.

The single-phase feed makes it possible to use a single overhead line. More overhead lines increase the costs, and restrict the maximum speed of train.

The asynchronous traction motor can run on a single RPM determined by the frequency of the feeding current and the loading torque. The solution was to use more secondary windings on phase converter, and more windings on motor different number of magnetic poles.

Types

A rotary phase converter (RPC) may be built as a motor-generator set. These completely isolate the load from the single-phase supply and produce balanced three-phase output. However, due to weight, cost, and efficiency concerns, most RPCs are not built this way.

Instead, they are built out of a three-phase induction motor or generator, called an idler, on which two of the terminals (the idler inputs) are powered from the single phase line. The rotating flux in the motor produces a voltage on the third terminal. A voltage is induced in the third terminal that is shifted by 120° from the voltage between the first two terminals. In a three-winding motor, two of the windings are acting as a motor, and the third winding is acting as a generator.

Power quality

A common measure of the quality of the power produced by an RPC or any phase converter is the voltage balance, which may be measured while the RPC is driving a balanced load such as a three-phase motor. Other quality measures include the harmonic content of the power produced and the power factor of the RPC motor combination as seen by the utility. Selection of the best phase converter for any application depends on the sensitivity of the load to these factors. Three-phase induction motors are very sensitive to voltage imbalances.

The quality of three-phase power generated by such a phase converter depends upon a number of factors including:

Quality improvement

RPC manufacturers use a variety of techniques to deal with these problems. Some of the techniques include,

How RPCs work

The main principles of RPC operation are as follows: Three-phase induction motors have three terminals called "legs", usually numbered (arbitrarily) L1, L2, and L3. A three-phase induction motor can be run at two-thirds of its rated horsepower on single-phase power applied to any pair of legs, once spun up by some means. A three-phase induction motor that is spinning under single-phase power applied to legs L1 and L2, generates an electric potential (and can deliver power through) leg L3, although without some form of current injection, special windings in the idler, or other means the voltage will sag when a load is applied. Power factor correction is a very important consideration when building or choosing an RPC. This is desirable because an RPC that has power factor correction will consume less current from the single-phase service supplying power to the phase converter and its loads. Balanced voltage between the three legs of power is important for operational life of the equipment receiving that power. Unbalanced three-phase power can damage the equipment that it is meant to operate.

Use of RPCs

General

RPCs may be used anywhere three-phase devices need to be used, but only single phase power is available. Three-phase motors cannot start on single phase power without a device to generate three-phase power. Since prices (and quality) of used three-phase motors are usually more favorable than those of their single-phase counterparts, demand exists for phase converters. This is also true because single-phase electric motors generally are not available in sizes over 15 hp (11 kW) due to their complexity, starting requirements and relative high expense and low efficiency compared to three-phase motors. In fact, single-phase motors larger than 5 hp (3.7 kW), though available, are rarely seen in use for these reasons. RPCs are sold by various vendors, but often also are home made.

Electric railways

Rotary phase converters are used in the opposite direction (three-phase to single-phase) for electric railways. In Europe, electricity is normally generated as three-phase AC at 50 Hertz. Five European countries, Germany, Austria, Switzerland, Norway and Sweden have standardised on single-phase AC at 15 kV 16⅔ Hz for railway electrification. Phase converters are, therefore, used to change both the phase and the frequency. In the Soviet Union they were used on AC locomotives to convert single phase, 50 Hertz to 3-phase for driving Induction motors for traction motor cooling blowers, etc.[1]

Alternatives to rotary converters

Alternatives exist to rotary phase converters for operation of three-phase equipment on a single-phase power supply.