Flammability limit

The standard reference work is that by Zabetakis using an apparatus developed by the United States Bureau of Mines.

Violence of combustion

Combustion can vary in degree of violence. A deflagration is a propagation of a combustion zone at a velocity less than the speed of sound in the unreacted medium. A detonation is a propagation of a combustion zone at a velocity greater than the speed of sound in the unreacted medium. An explosion is the bursting or rupture of an enclosure or container due to the development of internal pressure from a deflagration or detonation as defined in NFPA 69.

Limits

Lower explosive limit

Lower explosive limit (LEL): The lowest concentration (percentage) of a gas or a vapor in air capable of producing a flash of fire in presence of an ignition source (arc, flame, heat). The term is considered by many safety professionals to be the same as the lower flammable limit (LFL). At a concentration in air lower than the LEL, gas mixtures are "too lean" to burn. Methane gas has an LEL of 4.4%. If the atmosphere has less than 4.4% methane, an explosion cannot occur even if a source of ignition is present.

Percentage reading on combustible air monitors should not be confused with the LEL concentrations. Explosimeters designed and calibrated to a specific gas may show the relative concentration of the atmosphere to the LEL—the LEL being 100%. A 5% displayed LEL reading for methane, for example, would be equivalent to 5% multiplied by 4.4%, or approximately 0.22% methane by volume at 20 degrees C. Control of the explosion hazard is usually achieved by sufficient natural or mechanical ventilation, to limit the concentration of flammable gases or vapors to a maximum level of 25% of their lower explosive or flammable limit.

Upper explosive limit

Upper explosive limit (UEL): Highest concentration (percentage) of a gas or a vapor in air capable of producing a flash of fire in presence of an ignition source (arc, flame, heat). Concentrations higher than UFL or UEL are "too rich" to burn.

Influence of temperature, pressure and composition

Flammability limits of mixtures of several combustible gases can be calculated using Le Chatelier's mixing rule for combustible volume fractions xi:

LEL_{mix}=\frac{1}{\sum \frac{x_{i}}{LEL_{i}}}

and similar for UEL.

Temperature, pressure, and the concentration of the oxidizer also influences flammability limits. Higher temperature or pressure, as well as higher concentration of the oxidizer (primarily oxygen in air), results in lower LFL and higher UFL, hence the gas mixture will be easier to explode. The effect of pressure is very small at pressures below 10 millibar and difficult to predict, since it has only been studied in internal combustion engines with a turbocharger.

Usually atmospheric air supplies the oxygen for combustion, and limits assume the normal concentration of oxygen in air. Oxygen-enriched atmospheres enhance combustion, lowering the LFL and increasing the UFL, and vice versa; an atmosphere devoid of an oxidizer is neither flammable nor explosive for any fuel concentration. Significantly increasing the fraction of inert gases in an air mixture, at the expense of oxygen, decreases the LFL and increases the UFL.

Controlling explosive atmospheres

Gas and vapor

Controlling gas and vapor concentrations outside the explosive limits is a major consideration in occupational safety and health. Methods used to control the concentration of a potentially explosive gas or vapor include use of sweep gas, an unreactive gas such as nitrogen or argon to dilute the explosive gas before coming in contact with air. Use of scrubbers or adsorption resins to remove explosive gases before release are also common. Gases can also be maintained safely at concentrations above the UEL, although a breach in the storage container can lead to explosive conditions or intense fires.

Dusts

Dusts also have upper and lower explosion limits, though the upper limits are hard to measure and of little practical importance. Lower explosive limits for many organic materials are in the range of 1050 g/m³, which is much higher than the limits set for health reasons, as is the case for the LEL of many gases and vapours. Dust clouds of this concentration are hard to see through for more than a short distance, and normally only exist inside process equipment.

Explosion limits also depend on the particle size of the dust involved, and are not intrinsic properties of the material. In addition, a concentration above the LEL can be created suddenly from settled dust accumulations, so management by routine monitoring, as is done with gases and vapours, is of no value. The preferred method of managing combustible dust is by preventing accumulations of settled dust through process enclosure, ventilation, and surface cleaning. However, lower explosion limits may be relevant to plant design.

Examples

The flammable/explosive limits of some gases and vapors are given below. Concentrations are given in percent by volume of air.

Substance LFL/LEL in %

by volume of air

UFL/UEL in %

by volume of air

NFPA Class Flash point Minimum ignition energy in mJ

expressed at percent by volume in air

(Note, for many chemicals it
takes the least amount of
ignition energy midpoint between
the LEL and UEL.)[1]
Autoignition
temperature
Acetaldehyde 4.0 57.0 IA -39 °C 0.37 175 °C
Acetic acid (glacial) 4 19.9 II 39 °C to 43 °C 463 °C
Acetic anhydride II 54 °C
Acetone 2.6–3 12.8–13 IB -17 °C 1.15 @ 4.5% 465 °C, 485 °C[2]
Acetonitrile IB 2 °C 524 °C
Acetyl chloride 7.3 19 IB 5 °C 390 °C
Acetylene 2.5 100[3] IA Flammable gas 0.017 @ 8.5% (in pure oxygen 0.0002 @ 40%) 305 °C
Acrolein 2.8 31 IB -26 °C 0.13
Acrylonitrile 3.0 17.0 IB 0 °C 0.16 @ 9.0%
Allyl chloride 2.9 11.1 IB -32 °C 0.77
Ammonia 15 28 IIIB 11 °C 680 651 °C
Arsine 4.5–5.1[4] 78 IA Flammable gas
Benzene 1.2 7.8 IB -11 °C 0.2 @ 4.7% 560 °C
1,3-Butadiene 2.0 12 IA -85 °C 0.13 @ 5.2%
Butane, n-butane 1.6 8.4 IA -60 °C 0.25 @ 4.7% 420–500 °C
n-Butyl acetate, butyl acetate 1–1.7[2] 8–15 IB 24 °C 370 °C
Butyl alcohol, butanol 1 11 IC 29 °C
n-Butanol 1.4[2] 11.2 IC 35 °C 340 °C
n-Butyl chloride, 1-chlorobutane 1.8 10.1 IB -6 °C 1.24
n-Butyl mercaptan 1.4[5] 10.2 IB 2 °C 225 °C
Butyl methyl ketone, 2-hexanone 1[6] 8 IC 25 °C 423 °C
Butylene, 1-butylene, 1-butene 1.98[4] 9.65 IA -80 °C
Carbon disulfide 1.0 50.0 IB -30 °C 0.009 @ 7.8% 90 °C
Carbon monoxide 12[4] 75 IA -191 °C Flammable gas 609 °C
Chlorine monoxide IA Flammable gas
1-Chloro-1,1-difluoroethane 6.2 17.9 IA -65 °C Flammable gas
Cyanogen 6.0–6.6[7] 32–42.6 IA Flammable gas
Cyclobutane 1.8 11.1 IA -63.9 °C[8] 426.7 °C
Cyclohexane 1.3 7.8–8 IB -18 °C to -20 °C[9] 0.22 @ 3.8% 245 °C
Cyclohexanol 1 9 IIIA 68 °C 300 °C
Cyclohexanone 1–1.1 9–9.4 II 43.9–44 °C 420 °C[10]
Cyclopentadiene[11] IB 0 °C 0.67 640 °C
Cyclopentane 1.5–2 9.4 IB -37 to -38.9 °C[12][13] 0.54 361 °C
Cyclopropane 2.4 10.4 IA -94.4 °C[14] 0.17 @ 6.3% 498 °C
Decane 0.8 5.4 II 46.1 °C 210 °C
Diborane 0.8 88 IA -90 °C Flammable gas[15] 38 °C
o-Dichlorobenzene, 1,2-dichlorobenzene 2[16] 9 IIIA 65 °C 648 °C
1,1-Dichloroethane 6 11 IB 14 °C
1,2-Dichloroethane 6 16 IB 13 °C 413 °C
1,1-Dichloroethene 6.5 15.5 IA -10 °C Flammable gas
Dichlorofluoromethane 54.7 Non flammable,[17] -36.1 °C[18] 552 °C
Dichloromethane, methylene chloride 16 66 Non flammable
Dichlorosilane 4 - 4.7 96 IA -28 °C 0.015
Diesel fuel 0.6 7.5 IIIA >62 °C (143 °F) 210 °C
Diethanolamine 2 13 IB 169 °C
Diethylamine 1.8 10.1 IB -23 to -26 °C 312 °C
Diethyl disulfide 1.2 II 38.9 °C[19]
Diethyl ether 1.9–2 36–48 IA -45 °C 0.19 @ 5.1% 160–170 °C
Diethyl sulfide IB -10 °C[20]
1,1-Difluoroethane 3.7 18 IA -81.1 °C[21]
1,1-Difluoroethylene 5.5 21.3 -126.1 °C[22]
Diisobutyl ketone 1 6 49 °C
Diisopropyl ether 1 21 IB -28 °C
Dimethylamine 2.8 14.4 IA Flammable gas
1,1-Dimethylhydrazine IB
Dimethyl sulfide IA -49 °C
Dimethyl sulfoxide 2.6–3 42 IIIB 88–95 °C 215 °C
1,4-Dioxane 2 22 IB 12 °C
Epichlorohydrin 4 21 31 °C
Ethane 3[4] 12–12.4 IA Flammable gas -135 °C 515 °C
Ethanol, ethyl alcohol 3–3.3 19 IB 12.8 °C (55 °F) 365 °C
2-Ethoxyethanol 3 18 43 °C
2-Ethoxyethyl acetate 2 8 56 °C
Ethyl acetate 2 12 IA -4 °C 460 °C
Ethylamine 3.5 14 IA -17 °C
Ethylbenzene 1.0 7.1 15–20 °C
Ethylene 2.7 36 IA 0.07 490 °C
Ethylene glycol 3 22 111 °C
Ethylene oxide 3 100 IA −20 °C
Ethyl chloride 3.8[4] 15.4 IA −50 °C
Ethyl mercaptan IA
Fuel oil No.1 0.7[4] 5
Furan 2 14 IA -36 °C
Gasoline (100 octane) 1.4 7.6 IB < 40 °C (40 °F) 246–280 °C
Glycerol 3 19 199 °C
Heptane, n-heptane 1.05 6.7 -4 °C 0.24 @ 3.4% 204–215 °C
Hexane, n-hexane 1.1 7.5 -22 °C 0.24 @ 3.8% 225 °C, 233 °C[2]
Hydrogen 4/18.3[23] 75/59 IA Flammable gas 0.016 @ 28% (in pure oxygen 0.0012) 500–571 °C
Hydrogen sulfide 4.3 46 IA Flammable gas 0.068
Isobutane 1.8[4] 9.6 IA Flammable gas 462 °C
Isobutyl alcohol 2 11 28 °C
Isophorone 1 4 84 °C
Isopropyl alcohol, isopropanol 2[4] 12 IB 12 °C 398–399 °C; 425 °C[2]
Isopropyl chloride IA
Kerosene Jet A-1 0.6–0.7 4.9–5 II >38 °C (100 °F) as jet fuel 210 °C
Lithium hydride IA
2-Mercaptoethanol IIIA
Methane (natural gas) 5.0 15 IA Flammable gas 0.21 @ 8.5% 580 °C
Methyl acetate 3 16 -10 °C
Methyl alcohol, methanol 6–6.7[4] 36 IB 11 °C 385 °C; 455 °C[2]
Methylamine IA 8 °C
Methyl chloride 10.7[4] 17.4 IA -46 °C
Methyl ether IA −41 °C
Methyl ethyl ether IA
Methyl ethyl ketone 1.8[4] 10 IB -6 °C 505–515 °C[2]
Methyl formate IA
Methyl mercaptan 3.9 21.8 IA -53 °C
Mineral spirits 0.7[2] 6.5 38–43 °C 258 °C
Morpholine 1.8 10.8 IC 31–37.7 °C 310 °C
Naphthalene 0.9[4] 5.9 IIIA 79–87 °C
Neohexane 1.19[4] 7.58 −29 °C 425 °C
Nickel tetracarbonyl 2 34 4 °C 60 °C
Nitrobenzene 2 9 IIIA 88 °C
Nitromethane 7.3 22.2 35 °C 379 °C
Octane 1 7 13 °C
iso-Octane 0.79 5.94
Pentane 1.5 7.8 IA -40 to -49 °C as 2-Pentane 0.18 @ 4.4% 260 °C
n-Pentane 1.4 7.8 IA 0.28 @ 3.3%
iso-Pentane 1.32[4] 9.16 IA 420 °C
Phosphine IA
Propane 2.1 9.5–10.1 IA Flammable gas 0.25 @ 5.2% (in pure oxygen 0.0021) 480 °C
Propyl acetate 2 8 13 °C
Propylene 2.0 11.1 IA -108 °C 0.28 458 °C
Propylene oxide 2.3 36 IA
Pyridine 2 12 20 °C
Silane 1.5[4] 98 IA <21 °C
Styrene 1.1 6.1 IB 31–32.2 °C 490 °C
Tetrafluoroethylene IA
Tetrahydrofuran 2 12 IB -14 °C 321 °C
Toluene 1.2–1.27 6.75–7.1 IB 4.4 °C 0.24 @ 4.1% 480 °C; 535 °C[2]
Triethylborane -20 °C -20 °C
Trimethylamine IA Flammable gas
Trinitrobenzene IA
Turpentine 0.8[24] IC 35 °C
Vegetable oil IIIB 327 °C (620 °F)
Vinyl acetate 2.6 13.4 −8 °C
Vinyl chloride 3.6 33
Xylenes 0.9–1.0 6.7–7.0 IC 27–32 °C 0.2
m-Xylene 1.1[2] 7 IC 25 °C 525 °C
o-Xylene IC 17 °C
p-Xylene 1.0 6.0 IC 27.2 °C 530 °C

See also

References

  1. Britton, L. G “Using Material Data in Static Hazard Assessment.” as found in NFPA 77 - 2007 Appendix B
  2. 1 2 3 4 5 6 7 8 9 10 Working with modern hydrocarbon and oxygenated solvents: a guide to flammability American Chemistry Council Solvents Industry Group, pg. 7, January 2008
  3. Matheson Gas Products. Matheson Gas Data Book (PDF). p. 443. Retrieved 2013-10-30.
  4. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 "Gases - Explosive and Flammability Concentration Limits". Retrieved 2013-09-09.
  5. n-BUTYL MERCAPTAN ICSC: 0018
  6. 2-HEXANONE ICSC:0489
  7. Cyanogen
  8. Yaws, Carl L.; Braker, William; Matheson Gas Data Book Published by McGraw-Hill Professional, 2001 pg. 211
  9. Yaws, Carl L.; Braker, William; Matheson Gas Data Book Published by McGraw-Hill Professional, 2001 pg. 216
  10. CYCLOHEXANONE ICSC: 0425
  11. MSDS Cyclopentadiene
  12. Yaws, Carl L.; Braker, William; Matheson Gas Data Book Published by McGraw-Hill Professional, 2001 pg. 221
  13. CYCLOPENTANE ICSC: 0353
  14. Yaws, Carl L.; Braker, William; Matheson Gas Data Book Published by McGraw-Hill Professional, 2001 pg. 226
  15. Yaws, Carl L.; Braker, William; Matheson Gas Data Book Published by McGraw-Hill Professional, 2001 pg. 244
  16. Walsh (1989) Chemical Safety Data Sheets, Roy. Soc. Chem., Cambridge.
  17. Encyclopedia.airliquide.com
  18. Yaws, Carl L.; Braker, William; Matheson Gas Data Book Published by McGraw-Hill Professional, 2001 pg. 266
  19. Yaws, Carl L.; Braker, William; Matheson Gas Data Book Published by McGraw-Hill Professional, 2001 pg. 281
  20. Yaws, Carl L.; Braker, William; Matheson Gas Data Book Published by McGraw-Hill Professional, 2001 pg. 286
  21. Yaws, Carl L.; Braker, William; Matheson Gas Data Book Published by McGraw-Hill Professional, 2001 pg. 296
  22. Yaws, Carl L.; Braker, William; Matheson Gas Data Book Published by McGraw-Hill Professional, 2001 pg. 301
  23. http://environmentalchemistry.com/yogi/periodic/H.html
  24. Combustibles

Further reading

This article is issued from Wikipedia - version of the Tuesday, January 19, 2016. The text is available under the Creative Commons Attribution/Share Alike but additional terms may apply for the media files.