Dilution (equation)

Dilution is a reduction in the pH of a chemical (gas, vapor, solution). It is the process of decreasing the concentration of a solute in solution, usually simply by mixing with more solvent. To dilute a solution means to add more solvent without the addition of more solute. The resulting solution is thoroughly mixed so as to ensure that all parts of the solution are identical.

The same direct relationship applies to gases and vapors diluted in air for example. Although, thorough mixing of gases and vapors may not be as easily accomplished.

For example, if there are 10 grams of salt (the solute) dissolved in 1 litre of water (the solvent), this solution has a certain salt concentration/molarity. If one adds 1 litre of water to this solution the salt concentration is reduced. The diluted solution still contains 10 grams of salt/(0.171 moles of NaCl).

Mathematically this relationship can be shown in the equation:

 C_1\times V_1 = C_2\times V_2

Where:

C_1 = Initial concentration or molarity.
V_1 = Initial volume.
C_2 = Final concentration or molarity.
V_2 = Final volume

Basic Room Purge Equation

The Basic Room Purge Equation, is used in industrial hygiene. It determines the time required to reduce a known vapor concentration existing in a closed space to a lower vapor concentration. The equation can only be applied when the purged volume of vapor or gas is replaced with "clean" air or gas. For example, the equation can be used to calculate the time required at a certain ventilation rate to reduce a high carbon monoxide concentration in a room.

\ D_t=\left [ \frac{V}{Q} \right ] \cdot ln\left [ \frac{C_{initial}}{C_{ending}}\right ] \quad

Sometimes the equation is also written as:

\ ln\left [ \frac{C_{ending}}{C_{initial}}\right ] \quad={-}\frac{Q}{V} \cdot (t_{ending}-t_{initial})\quad  where t_{initial} = 0

D_t = Time required; the unit of time used is the same as is used for Q.

V = Air or gas volume of the closed space or room in cubic feet, cubic meters or liters

Q = Ventilation rate into or out of the room in cubic feet per minute, cubic meters per hour or liters per second

C_{initial} = Initial concentration of a vapor inside the room measured in ppm

C_{ending} = Final reduced concentration of the vapor inside the room in ppm

Dilution Ventilation Equation

The Basic Room Purge Equation can be used only for purge scenarios. In a scenario where a liquid continuously evaporates from a container in a ventilated room, a differential equation has to be used.

 {dC \over dt} = \frac{G - Q' C}{V}

Where the ventilation rate has been adjusted by a mixing factor K.

 Q' = \frac{Q}{K}

C = concentration of a gas

G = generation rate

V = room volume

Q' = adjusted ventilation rate of the volume

Welding

The dilution in welding terms is defined as the weight of the base metal melted divided by the total weight of the weld metal. For example, if we have a dilution of 0.40, the fraction of the weld metal that came from the consumable electrode is 0.60.

See also

References

    External links

    This article is issued from Wikipedia - version of the Thursday, September 10, 2015. The text is available under the Creative Commons Attribution/Share Alike but additional terms may apply for the media files.