SafetyBUS p
SafetyBUS p is a standard for failsafe fieldbus communication in automation technology.
Origin
SafetyBUS p was developed by Pilz GmbH & Co. KG between 1995 and 1999. The objective was to provide a fieldbus for data communication in terms of machinery safety .
Since 1999 the technology of SafetyBUS p has been managed by the user organisation Safety Network International e.V. (formally SafetyBUS p Club International e.V.), whose members work on the further development of SafetyBUS p.
Application
The main application of SafetyBUS p lies in the communication of data with safety-related content. SafetyBUS p can be used anywhere that communicated data has to be consistent in terms of time and content, in order to safeguard against danger. This danger may concern hazards to life and limb, but may also involve the protection of economic assets.
Typical application areas are:
- Factory automation (e.g. car production, presses)
- Transport technology (e.g. cable cars, fairground rides)
SafetyBUS p can be used on applications with safety-related requirements up to SIL 3 of IEC 61508 or Cat. 4 of EN 954-1.
Technology
Technically, SafetyBUS p is based on the fieldbus system CAN. In addition to OSI Layers 1 and 2, which are already defined in CAN for bit rate and security, SafetyBUS p adds additional mechanisms to safeguard transmission in Layers 2 and 7.
Fault mechanisms
The following mechanisms are used on SafetyBUS p to detect transmission errors and device errors:
- Sequential numbers
- Timeout
- Echo
- ID for transmitter and receiver
- Data security (CRC)
Technical details
The SafetyBUS p frame data, as determined by the technology, is as follows:
- Maximum 64 bus subscribers per network
- Up to 4000 I/O points per network
- Transmission rates 20 to 500 kBaud, depending on the network extension
- Individual network segments can extend to up to 3500 m
- Multiple network segments can be connected
- Guaranteed error reaction times of up to 20 ms can be achieved
- Suitable for applications in accordance with SIL 3 of IEC 61508 and Cat. 4 of EN 954-1
- Option to supply voltage to the devices via the bus cable
- Subnetworks can be implemented in wireless technology, with fibre-optic cables and as an infrared connection.
Devices
Only safety-related devices are used in SafetyBUS p networks. In general these are designed to be multi-channel internally. Safety-related use of the devices normally requires safety to be certified by authorised testing laboratories, who test the devices in accordance with the applicable standards and provisions. A functional inspection is carried out by the user organisation Safety Network International e.V.
Organisation
The user organisation SafetyBUS p Club International e.V. combines manufacturers and users of SafetyBUS p and has been in existence since 1999. In 2006 the organisation was renamed Safety Network International e.V. In addition to the international organisation there are also two other regional organisations: Japan was established in 2000, while USA was established in 2001. The organisation continues to develop the system, resulting in its successor, SafetyNET p.
Literature
- Winfried Gräf: Maschinensicherheit. Hüthig GmbH & Co. KG, Heidelberg 2004, ISBN 3-7785-2941-2
- Armin Schwarz und Matthias Brinkmann: Praxis Profiline - SafetyBUS p - Volume D/J/E. Vogel Industrie Medien GmbH & Co. KG, Würzburg 2004, ISBN 3-8259-1919-6
- Armin Schwarz und Matthias Brinkmann: Praxis Profiline - SafetyBUS p - Volume D/E. Vogel Industrie Medien GmbH & Co. KG, Würzburg 2002, ISBN 3-8259-1915-3
- EU machinery directive: 98/37/EG
- Working paper BIA: Prüfgrundsätzen für sichere Bussysteme
- Reinert, D.; Schaefer, M.: Sichere Bussysteme für die Automation. Hüthig, Heidelberg 2001. ISBN 3-7785-2797-5
External links
Organizations: