Operative temperature

From Wikipedia, the free encyclopedia

Operative temperature (t_{o}) is defined as a uniform temperature of a radiantly black enclosure in which an occupant would exchange the same amount of heat by radiation plus convection as in the actual nonuniform environment.[1] Some references also use the terms 'equivalent temperature" or 'effective temperature' to describe combined effects of convective and radiant heat transfer.[2] In design, operative temperature can be defined as the average of the mean radiant and ambient air temperatures, weighted by their respective heat transfer coefficients.[3] The instrument used for assessing environmental thermal comfort in terms of operative temperature is called a eupatheoscope and was invented by A. F. Dufton in 1929.[4] Mathematically, operative temperature can be shown as;

t_{o}={\frac  {(h_{r}t_{{mr}}+h_{c}t_{a})}{h_{r}+h_{c}}}

where,

h_{c} = convective heat transfer coefficient
h_{r} = linear radiative heat transfer coefficient
t_{a} = air temperature
t_{{mr}} = mean radiant temperature

It is also acceptable to approximate this relationship for occupants engaged in near sedentary physical activity (with metabolic rates between 1.0 met and 1.3 met), not in direct sunlight, and not exposed to air velocities greater than 0.20 m/s (40 fpm). [5]

t_{o}={\frac  {(t_{a}+t_{{mr}})}{2}}

where t_{a} and t_{{mr}} have the same meaning as above.

Application

Operative temperature is used in heat transfer and thermal comfort analysis in transportation and buildings.[6] Most psychrometric charts used in HVAC design only show the dry bulb temperature on the x-axis(abscissa), however, it is the operative temperature which is specified on the x-axis of the psychrometric chart illustrated in ANSI/ASHRAE Standard 55 – Thermal Environmental Conditions for Human occupancy.

See also

References

  1. ASHRAE Terminology, ASHRAE Handbook CD, 1999-2002
  2. Nilsson, H.O., Comfort Climate Evaluation with Thermal Manikin Methods and Computer Simulation Models, National Institute for Working Life, 2004, pg. 37
  3. Thermal Comfort, ASHRAE Handbook, Fundamentals, Ch. 9, pg.3, 2009
  4. Glossary of Meteorology, American Meteorological Society, < http://amsglossary.allenpress.com/glossary/browse?s=e&p=42>, accessed Sept 2010
  5. ANSI/ASHRAE Standard 55-2010, Thermal Environmental Conditions for Human Occupancy
  6. Dufton, A. F. The Equivalent Temperature of a room and its Measurement, Building Research Technical Paper No. 13. London, 1932


This article is issued from Wikipedia. The text is available under the Creative Commons Attribution/Share Alike; additional terms may apply for the media files.