[edit] Summary
Sprinkler branch pipe through-penetration with plasticsleeve - missing firestop in concrete fire separation. The branch pipe is a penetrant, as is the plastic sleeve, which is a code violation if left in place, unless subject to bounding with a firestop that permits such sleeving to be left in place.
[edit] Licensing
I, the copyright holder of this work, hereby release it into the public domain. This applies worldwide. In case this is not legally possible, |
File history
Click on a date/time to view the file as it appeared at that time.
Date/Time | Dimensions | User | Comment | |
---|---|---|---|---|
current | 01:33, 5 August 2006 | 1,574×2,362 (568 KB) | Ahering@cogeco.ca (Talk | contribs) | (Sprinkler branch pipe through-penetration with plasticsleeve - missing firestop in concrete fire separation. The branch pipe is a penetrant, as is the plastic sleeve, which is a code violation if left in place, unless subject t) |