Safety Integrity Level

From Wikipedia, the free encyclopedia

Safety Integrity Level (SIL) is defined as a relative level of risk-reduction provided by a safety function, or to specify a target level of risk reduction.

Four SIL levels are defined, with SIL4 being the most dependable and SIL1 being the least. A SIL is determined based on a number of quantitative factors in combination with qualitative factors such as development process and safety life cycle management. The requirements for a given SIL are not consistent among all of the functional safety standards.

Contents

[edit] IEC 61508 and IEC 61511

The international standard IEC 61508 defines SIL using requirements grouped into two broad categories: hardware safety integrity and systematic safety integrity. A device or system must meet the requirements for both categories to achieve a given SIL.

The SIL requirements for hardware safety integrity are based on a probabilistic analysis of the device. To achieve a given SIL, the device must have less than the specified probability of dangerous failure and have greater than the specified safe failure fraction. These failure probabilities are calculated by performing a Failure Modes and Effects Analysis (FMEA). The actual targets required vary depending on the likelihood of a demand, the complexity of the device(s), and types of redundancy used.

The SIL requirements for systematic safety integrity define a set of techniques and measures required to prevent systematic failures (bugs) from being designed into the device or system. These requirements can either be met by establishing a rigorous development process, or by establishing that the device has sufficient operating history to argue that it has been proven in use.

Electric and electronic devices can be certified for use in functional safety applications according to IEC 61508, providing application developers the evidence required to demonstrate that the application including the device is also compliant.

IEC 61511 is an application specific adaptation of IEC 61508 for the Process Industry sector. This standard is used in the petrochemical and hazardous chemical industries, among others.

[edit] SIL in Other Standards

The following standards also use SIL (defined differently) as a measure of reliability and/or risk reduction.

  • EN 50128
  • EN 50129
  • Defence Standard 00-56 Issue 2

[edit] See also

[edit] External links