Geomagnetically induced current

From Wikipedia, the free encyclopedia

Geomagnetically induced currents (GIC), affecting the normal operation of long technological conductor systems, are a manifestation at ground level of space weather. During space weather events (or geomagnetic storms) Earth's near space current systems experience large spatiotemporal variations reflected also in the variations of the Earth’s geomagnetic field. These variations induce currents (GIC) in conductors operated at the surface of Earth. Electric transmission grids and buried pipelines are common examples of such conductor systems. GIC can cause problems such as increased corrosion of pipeline steel and damaged high-voltage power transformers. GIC are one possible consequence of geomagnetic storms, which may also affect geophysical exploration surveys and oil and gas drilling operations.

Contents

[edit] Background

The Earth’s geomagnetic field varies over a wide range of timescales. The longer-term variations, typically occurring over decades to millennia, are predominantly the result of dynamo action in the Earth’s core. Geomagnetic variations on timescales of seconds to years also occur, due to dynamic processes in the ionosphere, magnetosphere and heliosphere. These changes are ultimately tied to variations associated with the solar activity (or sunspot) cycle and are manifestations of ‘Space Weather’.

The fact that the geomagnetic field does respond to solar conditions can be useful, for example in investigating Earth structure using magnetotellurics, but it also creates a hazard. This geomagnetic hazard is primarily a risk to technology, at least under the Earth’s protective atmospheric blanket [1].

[edit] The Risk to Ground Infrastructures from Geomagnetically Induced Currents

The basic principle for the generation of GIC: variations of the ionospheric currents (I(t)) generate an electric field (E(t)) driving GIC. Shown are also real GIC recordings from the Finnish natural gas pipeline.
The basic principle for the generation of GIC: variations of the ionospheric currents (I(t)) generate an electric field (E(t)) driving GIC. Shown are also real GIC recordings from the Finnish natural gas pipeline.

A time-varying magnetic field external to the Earth induces electric currents in the conducting ground. These currents create a secondary (internal) magnetic field. As a consequence of Faraday's law of induction, an electric field at the surface of the Earth is induced associated with time variations of the magnetic field. The surface electric field causes electrical currents, known as geomagnetically induced currents (GIC), to flow in any conducting structure, for example, a power or pipeline grid grounded in the Earth. This electric field, measured in V/km, acts as a voltage source across networks.

Examples of conducting networks are electrical power transmission grids, oil and gas pipelines, undersea communication cables, telephone and telegraph networks and railways. GIC are often described as being quasi direct current (DC), although the variation frequency of GIC is governed by the time variation of the electric field. For GIC to be a hazard to technology, the current has to be of a magnitude and occurrence frequency that makes the equipment susceptible to either immediate or cumulative damage. The size of the GIC in any network is governed by the electrical properties and the topology of the network. The largest magnetospheric-ionospheric current variations, resulting in the largest external magnetic field variations, occur during geomagnetic storms and it is then that the largest GIC occur. Significant variation periods are typically from seconds to about an hour, so the induction process involves the upper mantle and lithosphere. Since the largest magnetic field variations are observed at higher magnetic latitudes, GIC have been regularly measured in Canadian, Finnish and Scandinavian power grids and pipelines since the 1970s. GIC of tens to hundreds of Amperes have been recorded. GIC have also been recorded at mid-latitudes during major storms. There may even be a risk to low latitude areas, especially during a storm commencing suddenly because of the high, short-period rate of change of the field that occurs on the dayside of the Earth.

GIC have been known since the mid-1800s when it was noted that electrical telegraph systems could sometimes run without power during geomagnetic storms, described at the time as operating on the “celestial battery”, while at other times they were completely inoperative [2]. See also: Aurora (astronomy)

[edit] GIC in power grids

Modern electric power transmission systems consist of generating plants inter-connected by electrical circuits that operate at fixed transmission voltages controlled at substations. The grid voltages employed are largely dependent on the path length between these substations and 200kV-700kV system voltages are common. There is a trend towards higher voltages and lower line resistances to reduce transmission losses over longer and longer path lengths. Low line resistances produce a situation favourable to the flow of GIC. Power transformers have a magnetic circuit that is disrupted by the quasi-DC GIC: the field produced by the GIC offsets the operating point of the magnetic circuit and the transformer may go into half-cycle saturation. This produces a harmonic-rich AC waveform, localised heating and leads to high reactive power demands, inefficient power transmission and possible mis-operation of protective measures. Balancing the network in such situations requires significant additional reactive power capacity [3]. The magnitude of GIC that will cause significant problems to transformers varies with transformer type. Modern industry practice is to specify GIC tolerance levels on new transformers.

On 13 March 1989 a severe geomagnetic storm caused the collapse of the Hydro-Québec power grid in a matter of seconds as equipment protection relays tripped in a cascading sequence of events [4]. Six million people were left without power for nine hours, with significant economic loss. Since 1989 power companies in North America, the UK, Northern Europe and elsewhere have invested in evaluating the GIC risk and in developing mitigation strategies.

GIC risk can, to some extent, be reduced by capacitor blocking systems, maintenance schedule changes, additional on-demand generating capacity, and ultimately, load shedding. These options are expensive and sometimes impractical. The continued growth of high voltage power networks results in higher risk. This is partly due to the increase in the interconnectedness at higher voltages; connections in terms of power transmission to grids in the auroral zone, and grids operating closer to capacity than in the past.

To understand the flow of GIC in power grids and to advise on GIC risk, analysis of the quasi-DC properties of the grid is necessary [5]. This must be coupled with a geophysical model of the Earth that provides the driving surface electric field, determined by combining time-varying ionospheric source fields and a conductivity model of the Earth. Such analyses have been performed for North America, the UK and in Northern Europe. The complexity of power grids, the source ionospheric current systems and the 3D ground conductivity make an accurate analysis difficult [6]. By being able to analyse major storms and their consequences we can build a picture of the weak spots in a transmission system and run hypothetical event scenarios.

Grid management is also aided by space weather forecasts of major geomagnetic storms. This allows for mitigation strategies to be implemented. Solar observations provide a 1-3 day warning of an Earth-bound coronal mass ejection (CME), depending on CME speed. Following this, detection of the solar wind shock that precedes the CME in the solar wind, by spacecraft at the Lagrangian L1 point, gives a definite 20-60 minutes warning of a geomagnetic storm (again depending on local solar wind speed). The magnitude and arrival time of a CME after detection is unknown, although there is much research and model development within the space weather community.

[edit] GIC hazard in pipelines

Schematic illustration of the cathodic protection system used to protect pipeline from corrosion.
Schematic illustration of the cathodic protection system used to protect pipeline from corrosion.

Major pipeline networks exist at all latitudes and many systems are on a continental scale. Pipeline networks are constructed from steel to contain high-pressure liquid or gas and have corrosion resistant coatings. Weathering and other damage to the pipeline coating can result in the steel being exposed to moist air or to the ground, causing localised corrosion problems. Cathodic protection is used to maintain pipelines at a negative potential with respect to the ground. This minimises corrosion without allowing decomposition of the pipe coating. The operating potential is determined from the electro-chemical properties of the soil and Earth in the vicinity of the pipeline. The GIC hazard to pipelines is that GIC cause swings in the pipe-to-soil potential, increasing the rate of corrosion during major geomagnetic storms (Gummow, 2002). GIC risk is not a risk of catastrophic failure, but a reduced service life of the pipeline.

Pipeline networks are modelled in a similar manner to power grids, for example through distributed source transmission line models that provide the pipe-to-soil potential at any point along the pipe (Boteler, 1997; Pulkkinen et al., 2001). These models need to consider complicated pipeline topologies, including bends and branches, as well as electrical insulators (or flanges) that electrically isolate different sections. From a detailed knowledge of the pipeline response to GIC, pipeline engineers can understand the behaviour of the cathodic protection system even during a geomagnetic storm, when pipeline surveying and maintenance may be suspended.

[edit] See also

[edit] Footnotes and references

  1. ^ For recent reviews see, e.g., Lanzerotti, 2001; Pirjola et al, 2005
  2. ^ Boteler et al, 1998
  3. ^ Erinmez et al, 2002
  4. ^ Bolduc, 2002
  5. ^ Lehtinen and Pirjola, 1985
  6. ^ See Thomson et al, 2005

[edit] Further reading

  • Bolduc, L., GIC observations and studies in the Hydro-Québec power system. J. Atmos. Sol. Terr. Phys., 64(16), 1793-1802, 2002.
  • Boteler, D. H., Distributed source transmission line theory for electromagnetic induction studies. In Supplement of the Proceedings of the 12th International Zurich Symposium and Technical Exhibition on Electromagnetic Compatibility. pp. 401-408, 1997.
  • Boteler, D. H., Pirjola, R. J. and Nevanlinna, H., The effects of geomagnetic disturbances on electrical systems at the Earth’s surface. Adv. Space. Res., 22(1), 17-27, 1998.
  • Erinmez, I. A., Kappenman, J. G. and Radasky, W. A., Management of the geomagnetically induced current risks on the national grid company’s electric power transmission system. J. Atmos. Sol. Terr. Phys., 64(5-6), 743-756, 2002.
  • Gummow, R. A., GIC effects on pipeline corrosion and corrosion-control systems. J. Atmos. Sol. Terr. Phys., 64(16), 1755-1764, 2002.
  • Lanzerotti, L. J., Space weather effects on technologies. In Song, P., Singer, H. J., Siscoe, G. L. (eds.), Space Weather. American Geophysical Union, Geophysical Monograph, 125, pp. 11-22, 2001.
  • Lehtinen, M., and R. Pirjola, Currents produced in earthed conductor networks by geomagnetically-induced electric fields, Annales Geophysicae, 3, 4, 479-484, 1985.
  • Pirjola, R., Kauristie, K., Lappalainen, H. and Viljanen, A. and Pulkkinen A., Space weather risk. AGU Space Weather, 3, S02A02, doi:10.1029/2004SW000112, 2005.
  • Thomson, A. W. P., A. J. McKay, E. Clarke, and S. J. Reay, Surface electric fields and geomagnetically induced currents in the Scottish Power grid during the 30 October 2003 geomagnetic storm, AGU Space Weather, 3, S11002, doi:10.1029/2005SW000156, 2005.
  • Pulkkinen, A., R. Pirjola, D. Boteler, A. Viljanen, and I. Yegorov, Modelling of space weather effects on pipelines, Journal of Applied Geophysics, 48, 233-256, 2001.
  • Pulkkinen, A. Geomagnetic Induction During Highly Disturbed Space Weather Conditions: Studies of Ground Effects, PhD thesis, University of Helsinki, 2003. (available at eThesis)

[edit] External GIC links