Talk:Control of the National Grid (UK)
From Wikipedia, the free encyclopedia
[edit] Origin of content
The original material was added by User:Engineman to the National Grid UK page. I didn't even read it all, but it dwarfed the rest of the article, wasn't wikified, didn't use an encyclopedic voice, appeared to go into great detail regarding diesel engine operation, and appeared to include advocacy for wind power. I'm moved it here for others to clean up or remove as they see fit. - Crosbiesmith 15:30, 12 November 2006 (UTC)
Hi Crosbie Smith,
all good points which I hold my hand up to, it probably is a bit too much about diesel, and does contain wind advocacy, so I am quite happy to have it edited down...
However, I have not yet seen anywhere a proper description of how the UK and indeed other grids are controlled, and it will clearly be a surprise to many people that diesels are in fact in very wide spread use, along with automatically sheddable loads.
I feel it is also important for people to understand clearly the reason using deisels is so cheap - becasue they are already paid for, and they have to be tested on full load.Engineman 17:06, 12 November 2006 (UTC)
- This is terrific stuff! It'll get chopped up and bashed about as it is forced into Wikipedia style, but thanks for giving us this unprecedented level of detail about power supply management: it's fascinating. -- The Anome 19:55, 18 November 2006 (UTC)
fantastic piece of editing!....195.166.59.7 17:25, 24 November 2006 (UTC)
Having read this article a number of ocassions I have now started a major tidy up of its contents. There has been too much irrelevant information included which raises a wikipedia issues of accuracy and credibility. We need to stick to the point and not go overboard on the testing of this or that which should be detailed in a separate topic altogether. Additionally there is also nothing mentioned about voltage control. I would also agree that the title should be changed to UK National Grid (Control). Aquizard 13:30, 8 January 2007 (UTC)
[edit] Proposed Move
- How the UK National Grid is presently controlled → UK National Grid —(Discuss)— —LeSaint 04:33, 11 January 2007 (UTC)
How the UK National Grid is presently controlled - this name isn't exactly in the style of WP:NAME. How about moving it to Control of the UK National Grid - or UK National Grid (control)? I am sure that as long as it is linked to from UK National Grid then anyone who is interested, will find it?Garrie 01:52, 12 December 2006 (UTC)
- Agreed... "how it is controlled" is not a thing which an article can be written. IF there is a UK National Grid, perhaps everything ought to be there, and this information can be dedicated its own section titled "Present Control." LeSaint 04:28, 11 January 2007 (UTC)
[edit] Wessex Water
None of this material has any bearing at all on how the Grid is operated. What is it doing in the article? Really, it should all be removed. — BillC talk 01:30, 9 May 2007 (UTC)
Well its there because most commentators don;t have a clue that a) diesel generators have a significant role in controlling the national grid, even quite small ones of 150 kW, and that many large credible organizations like WW do this, so wroth going into some detail. Also only about 450 Mw of such diesels out of an actual installed capacity of 20 GW (but not grid connected) are used and these un used diesels could have a major role in dealing with renewables induced fluctuations.Engineman 15:30, 27 May 2007 (UTC)
- This creates some problems.
- The article title is "Control of the National Grid UK". Your description in your reply suggests that is is more about 'potential future sources for reserve generation in the UK'.
- The article contains about 4200 words, of which 2200 are about Wessex Water diesel generators reserve capacity. Reserve and frequency control constitute only a small part of grid control: topics such as the balancing mechanism, demand forecasting, transmission asset management, reactive reserve optimisation, transmission contingencies, pumped storage policy, load levelling, demand reduction, SCADA systems, and uplift management, just to name a few topics off the top of my head, all play a part in control of the national grid, but are all very subsidiary, if mentioned at all, in this article. As such, the article runs into big problems with WP:WEIGHT.
- It's completely unreferenced. "Content based on a talk given at an Open University Seminar" doesn't meet the requirements of WP:V. Who was at this talk and what did they say? Has anyone offered any significant alternative views? Is there any means of verifying the statements in this article? — BillC talk 22:17, 26 November 2007 (UTC)
[edit] Unreferenced
OK good points but all the speakers at the OU conference, including the one on diesels, have now had their presentations published in book form. they are all pretty authoritative, and edited by Professors Boyle and Elliot of the Open University.
"Renewable Electricity and the Grid - the challenge of variability" Pub Earthscan. London isbn 13:978-1-84407-418-1
The above based on a conference:
"Integrating renewables into the electricity system" A one day conference on Tuesday January 24th at the Open University, Milton Keynes.......http://eeru.open.ac.uk/conferences.htm - viewable on line. And the following conference / convention repeated pretty much the same thing - there is no real dispute about the contents veracity - it is well known amongst people who study this sort of thing.
Power Convention 2007 10 - 11 September Imperial College, London 2007 covers these points as well.
You can also look it up on the Transco Web site.
Regarding your other points about control not mentinoed yes you are right, but this is meant to be a starting point and I am waiting for other people to add to it. Don't see why I should write it all. But I would say even many experts are unaware of the role of instantaneously disconnected loads, and rapid start diesels.
Yes there is too much stuff on Wessex Water and any one can be free to cut it out. But it does need some reference to an authentic player such as WW in this market to indicate that it is a highly significant element. Engineman (talk) 16:21, 9 December 2007 (UTC)
[edit] "Reserve and frequency control constitute only a small part of grid control:"
i would tend to disagree with the above statement - its easy to control the national grid if the load changes only slowly and predictably - you just start more power stations / stop them, maintain a spinning reserve and allow the governors to do the control. The tricky bit is dealing with sudden changes - ie large power station outages, or sudden demand jumps. That is why Frequency Response and Reserve Service are so important. Engineman (talk) 20:27, 9 December 2007 (UTC)
The point that is not often brought out, is that the National Grid and all other grids have well established procedures to deal with intermittency - caused largely by the power stations themselves.Engineman (talk) 20:39, 9 December 2007 (UTC)
[edit] The article title is "Control of the National Grid UK". Your description in your reply suggests that is is more about 'potential future sources for reserve generation in the UK'
I think that's being a bit picky - that's a comment in the discussion, not the article itself.
I've had a look at the article and it seems to me to be packed full of a good description of how the UK grid controls itself on a daily basis, to meet varying loads with different kinds of plant. I am sure it can be tidied up a bit, but the basic facts are good, and no one who knows anything about the industry would dispute them. The talk upon which this article is based was reviewed by senior engineers who actually work for National Grid, some who were at the various presentations and what I said was considered by them unremarkable.Engineman (talk) 20:44, 9 December 2007 (UTC)
[edit] Wessex Water
I have had another look and yes it does contain far too much mention of Wessex Water. If cut quite a few out but it could do with someone else doing a bit more. It does merit some mention because it does give a clear account from a credible source - no other company has gone on record but its got far too much.
I suggest part of it could be hived off to say diesel generator? Engineman (talk) 14:38, 10 December 2007 (UTC)
[edit] Edited letter from National Grid
This gives quantities in recent tenders for Reserve etc:
Letter from National Grid contracts engineer:
David,
The latest STOR market report has data on how much reserve we procured in the first tender round can be found via the link below. For the first two seasons of this year there was just over 2 GW of accepted tenders with roughly two thirds from large generators (BM units) and a third from the demand side (non BM (NBM)) providers. The non-BM consisting of both back up generation and sites which can reduce their electricity demand (e.g. water pumping)
http://www.nationalgrid.com/NR/rdonlyres/883E5532-EE34-4C26-AA01-F679ADE3092F/16453/STORMIR0701.pdf
On frequency response the total demand side load is of the order 500-550MW. The link below is to the frequency tender report for June. Figure 9 shows the level of contracted secondary response, with base level around the 550 mark, being the contracted demand side sites
Regards
John
Fred xxxxxxxxxxxx
Senior Contract Developer