A Fire Test is a means of determining whether or not fire protection products meet minimum performance criteria as set out in a building code or other applicable legislation.
The following series of pictures show a typical fire test, on firestop products, using a 3 hour fire endurance and hose stream test with mixed results, run at ULC, the Canadian affiliate of Underwriters Laboratories, in Scarborough, Ontario, Canada. There are many different types of fire tests apart from those on firestops. Walls and floors themselves can be tested, closures within them, such as windows, fire doors, fire dampers, structural steel and more. Fire tests are conducted both on active fire protection and on passive fire protection items. Each have different test methods and scales. There are full scale, small scale and bench scale tests. There are tests on systems, such as the one below, but there are also tests on materials, such as intumescents, to be sure of components that may be used within a system.
Fire testing must consider all aplicable provisions of product certification. The resulting certification listings form the basis of bounding for field installations of the products.
A fire test can also mean an ad hoc test performed to gather information in order to understand a specific hazard, such as a construction or storage configuration. Tests can be bench scale (e.g., flammable liquid flash point), medium scale (e.g., storage commodity classification), or full scale (e.g., replication of an entire rack storage configuration). Typical information gathered from full scale testing is heat release rate vs. time, smoke production and species composition, radiant heat, and interaction with fire control or suppression systems.
Penetrants being hung. |
Penetrants have been hung. |
Firestop mortar being pumped into place. |
|
Furnace used in fire testing. Bottom pipes are gas jets. Middle row of pipes are shield for thermocouples. |
|||
Preparing for the hose stream. 30PSI pressure must be measured at the base of the nozzle. |
|||
The hose stream passed except for two locations where the water came through, making a fire-resistance rating impossible in the US, but not in Canada. The two penetrations shown were filled with intumescent laced rockwool, sealed on top with silicone caulking. The caulking let go from the sleeves during the hose stream test. |
Many fire tests are run by official laboratories for the purpose of product certification. However, some manufacturers of fire protection products also maintain their own facilities and run tests for R & D purposes before going to the expense and exposure of a test at a third party facility.
Private fire test furnace in Tulsa, Oklahoma, USA. This furnace is used primarily for internal Research and Development by the Nelson Firestop Company but may also be used for third party testing, if the test is witnessed by Underwriters Laboratories. There is an adjustable opening on this furnace that can be used for 4' x 4' as well as 6' x 6' slabs. The furnace can also be tilted 90° to be able to test either wall assemblies or floor assemblies. The laboratory is also equipped with a full 30PSI hose stream capability. |
The use of inadequate fire testing and lack of product certification on circuit integrity fireproofing of electrical wiring between nuclear reactors and control rooms in nuclear power plants led to the Thermo-Lag scandal, which became known as a result of disclosures by whistleblower Gerald W. Brown to the Nuclear Regulatory Commission, watchdog groups and the press.